Set the serial monitor to 115200 baud, with lines ending in a newline only (LF, not CR+LF).

Setpoints are in degrees C and durations in minutes. The setpoint and PID gains apply to both control loops.

Command Description Example
st=<value> Sets the setpoint, degrees C. st=25.5
dt=<value> Sets the process duration, minutes. dt=60
dt+<value> Increases the duration by that many minutes. dt+15
dt-<value> Decreases the duration by that many minutes. dt-10
rt=<value> Sets the remaining time, minutes. Only while active. rt=30
kp=<value> Sets the proportional gain. kp=2.5
ki=<value> Sets the integral gain. ki=0.1
kd=<value> Sets the derivative gain. kd=0.01
prep Sets the state to preparing. prep
active Sets the state to active. active
term Sets the state to terminating. term
standby Sets the state to standby. standby
eeprom=reset Partially resets the settings stored in EEPROM. eeprom=reset
eeprom=fullreset Fully resets the settings stored in EEPROM. eeprom=fullreset
Command Description Example
sudo Enters the manual state, in which the PID loops stop computing. sudo
o1=<value> In the manual state, sets relay 1’s duty, out of 255. o1=64
o2=<value> In the manual state, sets relay 2’s duty, out of 255. o2=64

Warning: in the manual state nothing regulates temperature. The duty you set drives the heaters directly.

  • Entering sudo does not zero the outputs. Each heater keeps its last PID output until you set it with o1= or o2=.
  • The firmware caps the outputs at 191.25 of 255. If either one is set above that, both are set to 191.25. So o1=255 also turns relay 2 up to 191.25, and relay 2 stays there until you send o2= or standby.
  • standby leaves the manual state and sets both outputs to 0.